Requirements (3)
ReferenceRequirementSourceClass
REQ-S-3300-18
The test medium shall be filtered potable water with a chloride content of not more than 30 ppm.
ZRF-SPC-3300mandatoryAccepted
REQ-S-3300-22
The test pressure shall be held for not less than 2 hours with no visible leakage and no pressure loss.
ZRF-SPC-3300mandatoryAccepted
REQ-SUG-001
Consider recording ambient temperature at the start and end of the hold period, to explain a pressure change that is thermal rather than a leak.
ZRF-SPC-3300informativeSuggested