Review comments

Every comment raised, its severity, its answer, and who may close it.

Demonstration project - no figure here describes a real facilityChanges are not saved
Why

Anybody may answer a comment. Only the reviewer who raised it may close it, which is enforced in the page, in the write service and by a database constraint.

Writes are validated against the engineering rules and then refused, because no database has been configured for this environment.

Comments

6

Open

2

Blocking and open

3

Closed

2

Clear
Review comments (4)
DeliverableSectionSeverityCommentRaised byResponseStateWho may close
ZRF-HTP-00156 ProcedureTechnical
The vent sequence appears to be missing between steps 6.4 and 6.5.
S. LindqvistWithdrawn: the vent is in 6.3 and I had read the steps out of order. No change needed.withdrawnonly S. Lindqvist
ZRF-HTP-00155.1Blocking
The test pressure basis cites the line list, which states 26 barg, while the datasheet for P-1201A states 24 barg. The derived test pressure cannot be stated until this is resolved.
N. OkonkwoAgreed. Raised as a reconciliation item against P-1201A; the section now states the gap.answeredonly N. Okonkwo
ZRF-HTP-00156.1Technical
The isolation list includes HV-1202, which is on the header and outside the test boundary for SYS-12-01.
N. OkonkwoRemoved from the isolation list at Rev B.closedclosed
ZRF-HTP-00159Blocking
Acceptance criteria state a 2 hour hold. Appendix D requires the hold to be witnessed; the procedure does not say who witnesses it or what they sign.
S. Lindqvistnot answeredopenonly S. Lindqvist

The author cannot close their own answer

Most review tools let them, which turns a review into a formality: the reviewer discovers at issue that their objection was closed by the person it was aimed at. Here, anybody may answer and only the raiser may close.

Answer a comment

Ticking close is refused unless you are the reviewer who raised it.

Blocking means blocking

It stops approval, not drafting. Why