ReferenceRequirementSourceClass
REQ-A-014
The hydrostatic test pressure shall be not less than 1.5 times the design pressure of the line under test.
ZRF-CTR-APX-AmandatoryAccepted
REQ-A-021
The Contractor shall submit every deliverable listed in the master document register for Company review before construction.
ZRF-CTR-APX-AmandatoryAccepted
REQ-D-003
An inspection and test plan shall be submitted for each work package, identifying every hold point and witness point.
ZRF-CTR-APX-DmandatoryAccepted
REQ-D-011
Pressure testing shall be witnessed by the Company representative and the record signed before reinstatement.
ZRF-CTR-APX-DmandatoryNot accepted
REQ-ISO-15649-9
Pressure testing requirements for piping systems. Clause text not reproduced: no licensed copy is held.
ISO 15649 not heldmandatoryNot accepted
REQ-S-3300-18
The test medium shall be filtered potable water with a chloride content of not more than 30 ppm.
ZRF-SPC-3300mandatoryAccepted
REQ-S-3300-22
The test pressure shall be held for not less than 2 hours with no visible leakage and no pressure loss.
ZRF-SPC-3300mandatoryAccepted
REQ-S-4100-07
Every instrument loop shall be checked from the field element to the control system indication before commissioning.
ZRF-SPC-4100mandatoryAccepted
REQ-SUG-001
Consider recording ambient temperature at the start and end of the hold period, to explain a pressure change that is thermal rather than a leak.
ZRF-SPC-3300informativeSuggested